# PLC_PRS10

> PLC_PRS10

Original author: UterGrooll (source: https://github.com/UterGrooll/PLC_PRS10)

## Article

## PLC_PRS10 — Arduino Modbus TCP Slave Controller for SCADA with W5100/W5500 and Ethernet Watchdog

**Tags:** W5100 · W5500 · Arduino · Modbus TCP · SCADA · PLC · DS18B20 · Relay Control · Industrial IoT

---

### Overview

**PLC_PRS10** is a compact, open-source PLC-style controller built on Arduino and WIZnet W5100/W5500 Ethernet. It acts as a **Modbus TCP Slave** device, exposing two relay outputs, a DS18B20 temperature reading, and four discrete digital inputs to any SCADA system — all over standard Modbus TCP on port 502.

The project is intentionally minimal: no RTOS, no cloud dependency, no configuration portal. It plugs into an existing Ethernet network, announces itself at a fixed IP, and immediately speaks Modbus TCP — the lingua franca of industrial automation. Tested with **Rapid SCADA** and **Modbus Poll**, it fits naturally into any supervisory control environment that supports Modbus TCP/IP.

A custom Modbus library ([`ModbusTCP_RU`](https://github.com/UterGrooll/ModbusTCP_RU)) handles the protocol stack, including a split Modbus data model that keeps coils, discrete inputs, and input registers in separate address spaces.

---

### Hardware Platform

| Component | Description |
| --- | --- |
| **MCU** | Arduino (ATmega328P) |
| **Ethernet** | WIZnet **W5100** or **W5500** — SPI, CS on D10 |
| **Relay outputs** | 2× relay — D7 (Relay 1), D6 (Relay 2) |
| **Digital inputs** | 4× discrete input — D2 / D3 / D4 / D5, INPUT_PULLUP |
| **Temperature** | DS18B20 1-Wire sensor on D9 |
| **Protocol** | Modbus TCP, port 502, Slave ID 1 |

![Схема](https://github.com/UterGrooll/PLC_PRS10/raw/main/screenshot/shematic.png)

### How WIZnet W5100/W5500 is Used

The W5100 or W5500 (selectable at hardware level — both are pin-compatible on SPI) is the **only network interface** in PLC_PRS10. It provides the full TCP/IP stack in hardware, so the Arduino's ATmega328P only needs to write and read socket data — no software networking code.

#### 1. Modbus TCP Server

![Modbus Poll](https://github.com/UterGrooll/PLC_PRS10/raw/main/screenshot/Modbus%20Poll.png)

On startup, the firmware initialises the WIZnet chip with a static IP and immediately opens a Modbus TCP server on port 502:

```cpp
byte mac[] = { 0xDE, 0xDD, 0xBE, 0xEF, 0xFE, 0x01 }; 
IPAddress ip(192, 168, 1, 179); 
Ethernet.begin(mac, ip, gateway, subnet); 
MbServer.begin();
```

From this point the device is addressable by any SCADA system as a standard Modbus TCP slave. The SCADA polls at 1000 ms scan rate with a 1000 ms timeout — well within what the W5100/W5500 can handle while the Arduino simultaneously manages relay timing, debounces inputs, and reads the DS18B20.

#### 2. Ethernet Watchdog — Link Recovery Without Reboot

One of the most practical engineering decisions in this project is the **Ethernet link watchdog**. When a patch cord is disconnected and reconnected, the W5100/W5500 may respond to ARP/ping again, but its internal TCP server socket does not automatically recover — the SCADA master loses the Modbus TCP connection and the Arduino must be manually rebooted to restore it.

The watchdog solves this by monitoring the W5100/W5500 link status bit. When `LinkON` is detected after a link loss, the firmware reinitialises the Ethernet stack and restarts the Modbus server without rebooting the board:

```cpp
if (Ethernet.linkStatus() == LinkON && !linkWasOn) {     
    Ethernet.begin(mac, ip, gateway, subnet);     
    MbServer.begin();     
    linkWasOn = true; 
 }
```

This is critical for unattended deployment in cabinets or remote panels where physical reboots are not practical.

### Modbus Register Map

The firmware uses the `ModbusTCP_RU` library, which implements a **split data model** — coils, discrete inputs, and input registers occupy separate address spaces, matching standard Modbus conventions.

![Rapid SCADA](https://github.com/UterGrooll/PLC_PRS10/raw/main/screenshot/Rapid%20Scada.png)

#### Coils — FC01 (read) / FC05 or FC15 (write)

| Address | Signal | Values |
| --- | --- | --- |
| `0` | Relay 1 (D7) | `0 = OFF`, `1 = ON` |
| `1` | Relay 2 (D6) | `0 = OFF`, `1 = ON` |

Relay 1 includes a **hardware safety timer**: it automatically de-energises after 60 seconds regardless of the SCADA command state. This protects actuators (pumps, solenoids, heaters) from being left on indefinitely due to a SCADA crash or network fault.

#### Discrete Inputs — FC02 (read)

| Address | Signal | Pin | Logic |
| --- | --- | --- | --- |
| `0` | DI1 | D2 | `1 = closed`, `0 = open` |
| `1` | DI2 | D3 | `1 = closed`, `0 = open` |
| `2` | DI3 | D4 | `1 = closed`, `0 = open` |
| `3` | DI4 | D5 | `1 = closed`, `0 = open` |

Inputs use `INPUT_PULLUP`, so the active hardware state is LOW — the firmware inverts the reading before placing it in the Modbus registers so the SCADA sees `1 = closed` as expected.

#### Input Registers — FC04 (read)

| Address | Signal | Format | Example |
| --- | --- | --- | --- |
| `0` | DS18B20 temperature | °C × 10 (integer) | `253` = 25.3 °C |

Storing temperature as an integer scaled by 10 is a standard Modbus convention for floating-point-free devices — the SCADA applies a ×0.1 scale factor on its end.

### SCADA Integration

The device is tested and confirmed working with **Rapid SCADA** and **Modbus Poll**. The connection parameters are fixed and require no discovery protocol:

| Parameter | Value |
| --- | --- |
| Mode | Modbus TCP/IP |
| Server IP | `192.168.1.179` |
| Port | `502` |
| Slave ID | `1` |
| Timeout | 1000 ms |
| Scan Rate | 1000 ms |

Any SCADA, HMI, or PLC that supports Modbus TCP can connect using the same parameters — including Siemens WinCC, AVEVA InTouch, Ignition, Node-RED, and Home Assistant (via Modbus integration).

### Firmware Architecture

The sketch is a simple cooperative loop — no RTOS, no interrupts for networking (the W5100/W5500 handles all of that in hardware):

```plaintext
setup():
  - Initialise W5100/W5500 via SPI
  - Start Modbus TCP server on port 502
  - Initialise DS18B20
 loop():
  - Check Ethernet link watchdog → reinit if link recovered
  - Poll Modbus TCP server → process FC01/FC02/FC04/FC05/FC15
  - Update relay outputs from coil registers
  - Check Relay 1 auto-off timer (60 s)
  - Read DS18B20 → write to input register 0
  - Read DI1–DI4 → write to discrete input registers 0–3
```

The W5100/W5500 hardware TCP/IP stack handles all connection management, packet framing, and checksums. The Arduino only reads and writes register values — the networking burden is essentially zero on the MCU side.

#### Dependencies

| Library | Purpose |
| --- | --- |
| `SPI` | Arduino SPI bus (for W5100/W5500) |
| `Ethernet` | Arduino Ethernet driver for W5100/W5500 |
| [`ModbusTCP_RU`](https://github.com/UterGrooll/ModbusTCP_RU) | Custom Modbus TCP slave stack |
| `GyverDS18` | DS18B20 1-Wire temperature reading |

### Why W5100/W5500 for This Application?

An Arduino running a software TCP/IP stack (e.g. ENC28J60 with UIPEthernet) would consume most of the ATmega328P's 2 KB SRAM just for networking buffers, leaving almost nothing for application logic. The W5100/W5500 offloads the entire stack to dedicated hardware — the Arduino only exchanges socket data over SPI. This is why a 32 KB Flash / 2 KB SRAM microcontroller can simultaneously maintain a Modbus TCP server, manage relay timers, read a 1-Wire sensor, and monitor four digital inputs without any resource conflicts.

The W5500 in particular adds half-duplex/full-duplex auto-negotiation and a lower power draw than the W5100, making it the preferred choice for always-on cabinet installations.

### Application Fields

PLC_PRS10 fits directly into:

- **Building automation** — relay control and room temperature monitoring via SCADA

- **HVAC and heating systems** — thermostat-style relay switching with temperature feedback

- **Industrial panel I/O** — reading discrete signals from limit switches, door contacts, or pushbuttons into SCADA

- **Small pump and motor control** — relay actuation with safety auto-off timer

- **Remote monitoring stations** — Ethernet-connected sensor node in a factory or utility building

- **Educational and prototyping platforms** — full Modbus TCP stack on Arduino for learning industrial protocols

---

### FAQ

**Q: Can I use a W5500 module instead of a W5100 shield?** A: Yes — both use the same SPI interface and CS pin (D10). The `Ethernet.h` library supports both chips transparently. The W5500 offers slightly lower power consumption and better SPI throughput.

**Q: Why does the Ethernet watchdog matter in practice?** A: In industrial environments, cable connections are frequently disturbed — maintenance workers unplug and replug patch cords, power cycling resets switches. Without the watchdog, each cable event would require a physical Arduino reboot to restore the Modbus TCP server. With it, the device recovers automatically within seconds of link restoration.

**Q: Does the 60-second Relay 1 auto-off work independently of SCADA?** A: Yes — the timer runs on the Arduino itself. Even if the SCADA crashes or the network goes down while Relay 1 is energised, the Arduino will de-energise it after 60 seconds. This is an intentional failsafe.

**Q: What SCADA systems are supported?** A: Any system with a Modbus TCP driver — including Rapid SCADA (tested), Modbus Poll (tested), Siemens WinCC, AVEVA InTouch, Ignition, Node-RED, and Home Assistant.

---